J. Schneider C-TEC 2425 P

J. Schneider C-TEC 4815 P

J. Schneider C-TEC 2425 P, Capacitor buffered Power Supply. The DC UPS of the C-TEC 2425 P series is equipped with integrated ultracapacitors for accumulating energy. During normal operation this capacitor is charged by an internal charger which is supplied by an external, regulated DC power supply. If the DC supply is interrupted, energy of the ultracapacitors is released in a unregulated process (24,25 to 19 V DC). The load is supplied by the buffermodul until the voltage is ≤ 19 V. The buffering time depends on the state of charge of the capacitor and discharging current. As further function the C-TEC 2425 P can provide more current for a certain time.

The DC-UPS shows the following features:

  • Maintenance-free due to durable ultra capacitors
  • reduces wiring time due to intergrated energy storage
  • Microcontroller based charging and discharging of the ultracapacitors
  • Input voltage-signal via potential-free contact and LED
  • Short overload possible
  • Vibration secured wiring via spring loaded plugs
  • Wide working temperature range -40°C till 60°C

J. Schneider C-TEC 2425 P Technical Data

Nominal input voltage 24 V DC ±10 %
Min. nominal input voltage for charging mode 22 V DC
Max. nominal input current 28 A DC
Max. charging current 3 A DC
Nominal output voltage (mains operation) 24 V DC ±10 %
Nominal output voltage (buffer operation) 24,5 V … 19 V DC ± 2 %
Max. nominal output current 25 A DC
Efficiency > 90 %
Parallel connection No
Series connection No
Energy content 1,2 kJ
Buffer time 47 sec @ 1 A / 1 sec @ 25 A
Degree of protection IP20
Operating temperature -40 … 60 °C
Storage temperature -40 … 60 °C
Relative humidity 95 % non-condensing
Max. altitude (without derating) 2000 m above sealevel
Dimensions (H x W x D) 123 mm x 65 mm x 145 mm
Weight 0,8 kg
Fixation Snap-on mounting for DIN top hat rail

or mounting bracket for mounting plate

Norms and Regulations EN 50178 / EN 60950

EN 61000-6-4

EN 61000-6-2

EN 60068-2-6

EN 600068-2-27

UL approvals UL 508

C22.2

Source: Indonesia Industrial Parts – Measurement, Equipment, Electrical & Control (inaparts.com)

Download : Datasheet

Other Article:

Tinggalkan Balasan

Please log in using one of these methods to post your comment:

Logo WordPress.com

You are commenting using your WordPress.com account. Logout /  Ubah )

Gambar Twitter

You are commenting using your Twitter account. Logout /  Ubah )

Foto Facebook

You are commenting using your Facebook account. Logout /  Ubah )

Connecting to %s