Digital multiset measurement is a meta-analysis of the electrical energy to overall arrangements and plants, and distribution automation applied to all panel instrument and monitoring functions. These items are used for network communication features and traditional analog measurement of a meta to the various power monitoring in an integrated way is a versatile measuring device.
Feature
Variety of measurement Factor :
- Three-Phase Alternating Current: Phase Voltage, Line Voltage, Alternating Phase Current, Power Factor, Frequency
- Electric Power: Active Power, Reactive Power, Apparent power.
- Electric Energy: Active Power Value, Reactive Power Value, Inductive Electric Energy.
Minimum Measurement/Maximum Measurement Ranges
- Voltage (Phase/line), Current (Each Phase/Total)
- Active Electric Power (Each phase.total), Reactive Power (Each Phase/Total), Apparent Power (Each Phase/Total)
- Load Factor Mean
Deman Value
- Electric Power time (1-30 minutes, choice of the unit) is configurable
Pulse Output Remote control measurement
- Digital input: 2 Points, Modbus communication sent to the upper system
- Pulse output: 2 Points, Different output pulse energy
Communication Network Transmission
- Modbus Communication Protocol support
- Number of access is 31 devices
- Measurement values from a remote PC monitor is available at the main set
Operation Input and Output
- Easy to measure with simple operation
- Possible to replace wiring part without losing out it
- Can be fixed without screw because of the panel mounting attachment
- LED Display for R,S,T
- Phase Display
- Kilo/Mega (KV,KA,KW/MV, MA, MW) display LED
- Up Button – Optional PartDown Button – Optional Part
- Total mean Load of a Display monitor
- H: MAX, Display LEDL: MIN, Display LEDM: Demand, Display LED
- Set Button
- Press SET Button for 3 seconds, Program would be started
- Move to the instantaneous value
- Move to SAVE menu
- ESC Button:
- MINIMUM LED, MAX LED
- Move to the instantaneous value
- Move to SAVE menu
Specification
Model | YSPM-07 | YSPM-07S | |
Communication interface | General Type | Communication Interface | |
Auxiliary Power | 190 – 260 AC±10% 45- 65 Hz, 4VA | ||
Connection Type | 3-phase / 4-wire | ||
3-phase / 3-wire | |||
Rate Input | Voltage | 10 -300,0 VAC (L-N), 10-500,0 VAC (L-L) | |
Current | 0,05 A – 5,5 A | ||
Power Consumption | Below 1,0 VA | ||
Measurement Range | Voltage | 11V – 440.000 V | |
Current | 5A- 10.000 A | ||
Frequency | 45- 64 Hz | ||
Demand Time | 1-15 minutes(mean value between measured value) | ||
Digital Input | Input | 2 Digital Inputs | |
Operating Voltage/current | DC12-48 V Max. DC30V 50mA | ||
Pulse Output | Output Ratio | 1,10,100 (Wh/ Varh/ VA) : 1,10,100 (kWh/kVarh/kVA :1(MWh/MVarh/MVA) | |
Pulse Width | NPN Transistor 80msec | ||
Operating Voltage | 5-24VDC MAX. 30VDC: MAX 50 mA | ||
Communication Interface | Protokol | – | Modbus RTU |
Port | – | RS-485 2 wire:1port | |
Communication interface speed | – | 2,400-38,400 bps | |
Display | Red LED: 10 mm Height | ||
Dimension | 96,0 X 96,0X 79,3 (WxHxD :mm) | ||
Weight | 0,54 kg | ||
Applied Standart | IEC-60255 |