Complementary |
---|
reset time | <= 1500 ms for at 480 V |
maximum switching voltage | 250 V AC |
250 V DC |
minimum switching current | 10 mA at 5 V DC |
maximum switching current | 5 A AC |
5 A DC |
supply voltage limits | 194…528 V AC, 3 phases |
batas control circuit voltage | – 12 % + 10 % Un |
komsumdi daya VA | 0…22 VA at 400 V AC 50 Hz |
voltage detection threshold | < 194 V |
control circuit frequency | 50…60 Hz +/- 10 % |
output contacts | 2 C/O |
nominal output current | 5 A |
measurement voltage limits | 176…528 V AC |
hysteresis | 2 % |
delay at power-up | <= 650 ms |
measuring cycle | <= 140 ms measurement cycle as true rms value |
threshold adjustment voltage | +2…+10 % in the range 480 V AC |
-12…-2 % in the range 220 V AC |
2…20 % of Unselected |
-20…-2 % in the range 380…480 V AC |
+2…+20 % in the range 220…440 V AC |
voltage range | 220…480 V phase to phase |
adjustment of asymmetry threshold | 5…15 % of Unselected |
repeat accuracy | 0.3 % for time delay |
0.5 % for input and measurement circuit |
measurement error | < 1 % over the whole range with a voltage variation |
0.05 %/°C with temperature variation |
response time | < 200 ms in the event of a fault |
marking | CE |
overvoltage category | III conforming to IEC 60664-1 |
insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
> 500 MOhm at 500 V DC conforming to IEC 60664-1 |
[Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
supply frequency | 50/60 Hz +/- 10 % |
operating position | Any position without |
connections – terminals | Screw terminals 1 x 0.5…1 x 4 mm² – AWG 20…AWG 11, solid cable without cable end |
Screw terminals 2 x 0.5…2 x 2.5 mm² – AWG 20…AWG 14, solid cable without cable end |
Screw terminals 1 x 0.2…1 x 2.5 mm² – AWG 24…AWG 12, flexible cable with the cable end |
Screw terminals 2 x 0.2…2 x 1.5 mm² – AWG 24…AWG 16, flexible cable with the cable end |
tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
housing material | Self-extinguishing plastic |
local signaling | LED green for power ON |
LED yellow for relay ON |
LED yellow for fault |
mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
electrical durability | 100000 cycles |
mechanical durability | <= 30000000 cycles |
operating rate | <= 360 operations/hour under full load |
utilization category | AC-12 conforming to IEC 60947-5-1 |
AC-13 conforming to IEC 60947-5-1 |
AC-14 conforming to IEC 60947-5-1 |
AC-15 conforming to IEC 60947-5-1 |
DC-12 conforming to IEC 60947-5-1 |
DC-13 conforming to IEC 60947-5-1 |
safety reliability data | MTTFd = 399.5 years |
B10d = 360000 |
width | 35 mm |
product weight | 0.13 kg |