Remote Set Point Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
Type | Linear Current, Linear Voltage | ||||||
Range | -3 mA to 27 mA, -1.3 VDC to 11.5 VDC | ||||||
Accuracy | ± 0.05% | ||||||
Remote Set Point Option | Not Available | Available | Not Available | ||||
Input Impedance | Current : 2.5 Ω, Voltage : 1.5 MΩ | ||||||
Resolution | 18 Bits | ||||||
Sampling Rate | 1.66 Times / Second | ||||||
Maximum Rating | 280 mA maximum for Current Input, 12 VDC maximum for Voltage Input | ||||||
Temperature Effect | ±1.5 μV /°C for Voltage Input, ± 3.0 μV /°C for Current Input | ||||||
Sensor Break Detection | Below 1 mA for 4 – 20 mA input, below 0.25 VDC for 1 – 5 VDC input, not available for other inputs | ||||||
Sensor Break Responding Time | 0.1 second |
Event Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Number of Event Input | 1 | 2 | 6 | 6 | 2 | 6 | 2 |
Logic Low | -10 VDC minimum, 0.8 VDC maximum | ||||||
Logic High | 2 VDC minimum, 10 VDC maximum | ||||||
Function | Refer to the user manual |
CT Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
CT Type | CT98-1 | ||||||
Accuracy | ± 5 % of Full-Scale Reading, ± 1 digit maximum | ||||||
Input Impedance | 294 Ω | ||||||
Measurement Range | 0 to 50 A-VAC | ||||||
Output of CT | 0 to 5 VDC | ||||||
Sampling Rate | 1 Time / Second |
Output 1 / Output 2
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Type | Relay, Pulsed Voltage, Linear Voltage, and Linear Current | ||||||
Relay Rating | 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load | ||||||
Pulsed Voltage | Source Voltage 5 VDC, Current Limiting Resistance 66 Ω | ||||||
Linear Output Resolution | 15 Bits | ||||||
Linear Output Regulation | 0.02 % for full load change | ||||||
Linear Output Settling Time | 0.1 Second (Stable to 99.9 %) | ||||||
Isolation Breakdown Voltage | 1,000 V AC | ||||||
Temperature Effect | ± 0.01% of Span /°C | ||||||
Load Capacity of Linear Output | Linear Current 500 Ω maximum, Linear Voltage10 KΩ minimum |
Alarm
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
Maximum Rating | 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load | ||||||
Alarm Function | Dwell Timer, Deviation Low, Deviation High, Deviation Band Low, Deviation Band High, Process High, Process Low, Range Low, Range High, Range High Low, Heater Break, Heater Short, Profile End, Profile Holdback | ||||||
Alarm Mode | Latching, Holding, Normal, Latching / Holding, Set Point Holding | ||||||
Dwell Timer | 0.1 to 4,553.6 Minutes |