Brainchild temperature controll
Brainchild temperature controll

Brainchild Electronic

7 minutes, 22 seconds Read

Remote Set Point Input

Model C22 C62 C82 C83 C72 C42 R22
Type Linear Current, Linear Voltage
Range -3 mA to 27 mA, -1.3 VDC to 11.5 VDC
Accuracy ± 0.05%
Remote Set Point Option Not Available Available Not Available
Input Impedance Current : 2.5 Ω, Voltage : 1.5 MΩ
Resolution 18 Bits
Sampling Rate 1.66 Times / Second
Maximum Rating 280 mA maximum for Current Input, 12 VDC maximum for Voltage Input
Temperature Effect ±1.5 μV /°C for Voltage Input, ± 3.0 μV /°C for Current Input
Sensor Break Detection Below 1 mA for 4 – 20 mA input, below 0.25 VDC for 1 – 5 VDC input, not available for other inputs
Sensor Break Responding Time 0.1 second

Event Input

Model C22 C62 C82 C83 C72 C42 R22
Number of Event Input 1 2 6 6 2 6 2
Logic Low -10 VDC minimum, 0.8 VDC maximum
Logic High 2 VDC minimum, 10 VDC maximum
Function Refer to the user manual

CT Input

Model C22 C62 C82 C83 C72 C42 R22
CT Type CT98-1
Accuracy ± 5 % of Full-Scale Reading, ± 1 digit maximum
Input Impedance 294 Ω
Measurement Range 0 to 50 A-VAC
Output of CT 0 to 5 VDC
Sampling Rate 1 Time / Second

Output 1 / Output 2

Model C22 C62 C82 C83 C72 C42 R22
Type Relay, Pulsed Voltage, Linear Voltage, and Linear Current
Relay Rating 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load
Pulsed Voltage Source Voltage 5 VDC, Current Limiting Resistance 66 Ω
Linear Output Resolution 15 Bits
Linear Output Regulation 0.02 % for full load change
Linear Output Settling Time 0.1 Second (Stable to 99.9 %)
Isolation Breakdown Voltage 1,000 V AC
Temperature Effect ± 0.01% of Span /°C
Load Capacity of Linear Output Linear Current 500 Ω maximum, Linear Voltage10 KΩ minimum

Alarm

Model C22 C62 C82 C83 C72 C42 R22
Maximum Rating 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load
Alarm Function Dwell Timer, Deviation Low, Deviation High, Deviation Band Low, Deviation Band High, Process High, Process Low, Range Low, Range High, Range High Low, Heater Break, Heater Short, Profile End, Profile Holdback
Alarm Mode Latching, Holding, Normal, Latching / Holding, Set Point Holding
Dwell Timer 0.1 to 4,553.6 Minutes

Similar Posts

Leave a Reply

Your email address will not be published. Required fields are marked *