Remote Set Point Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Type | Linear Current, Linear Voltage | ||||||
Range | -3 mA to 27 mA, -1.3 VDC to 11.5 VDC | ||||||
Accuracy | ± 0.05% | ||||||
Remote Set Point Option | Not Available | Available | Not Available | ||||
Input Impedance | Current : 2.5 Ω, Voltage : 1.5 MΩ | ||||||
Resolution | 18 Bits | ||||||
Sampling Rate | 1.66 Times / Second | ||||||
Maximum Rating | 280 mA maximum for Current Input, 12 VDC maximum for Voltage Input | ||||||
Temperature Effect | ±1.5 μV /°C for Voltage Input, ± 3.0 μV /°C for Current Input | ||||||
Sensor Break Detection | Below 1 mA for 4 – 20 mA input, below 0.25 VDC for 1 – 5 VDC input, not available for other inputs | ||||||
Sensor Break Responding Time |
0.1 second |
Event Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Number of Event Input | 1 | 2 | 6 | 6 | 2 | 6 | 2 |
Logic Low | -10 VDC minimum, 0.8 VDC maximum | ||||||
Logic High | 2 VDC minimum, 10 VDC maximum | ||||||
Function | Refer to user manual |
CT Input
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
CT Type | CT98-1 | ||||||
Accuracy | ± 5 % of Full Scale Reading, ± 1 digit maximum | ||||||
Input Impedance | 294 Ω | ||||||
Measurement Range | 0 to 50 A VAC | ||||||
Output of CT | 0 to 5 VDC | ||||||
Sampling Rate | 1 Time / Second |
Output 1 / Output 2
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Type | Relay, Pulsed Voltage, Linear Voltage and Linear Current | ||||||
Relay Rating | 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load | ||||||
Pulsed Voltage | Source Voltage 5 VDC, Current Limiting Resistance 66 Ω | ||||||
Linear Output Resolution | 15 Bits | ||||||
Linear Output Regulation | 0.02 % for full load change | ||||||
Linear Output Settling Time | 0.1 Second (Stable to 99.9 %) | ||||||
Isolation Breakdown Voltage | 1,000 V AC | ||||||
Temperature Effect | ± 0.01% of Span /°C | ||||||
Load Capacity of Linear Output | Linear Current 500 Ω maximum, Linear Voltage10 KΩ minimum |
Alarm
Model | C22 | C62 | C82 | C83 | C72 | C42 | R22 |
---|---|---|---|---|---|---|---|
Maximum Rating | 2 A, 240 V AC, 200,000 Life Cycles for Resistive Load | ||||||
Alarm Function | Dwell Timer,Deviation Low, Deviation High, Deviation Band Low, Deviation Band High, Process High, Process Low, Range Low, Range High, Range High Low, Heater Break, Heater Short, Profile End, Profile Holdback | ||||||
Alarm Mode | Latching, Holding, Normal, Latching / Holding, Set Point Holding | ||||||
Dwell Timer | 0.1 to 4,553.6 Minutes |