Igema Multifunctional system LW

2-point water level controller DLR1DHR1
Igema Multifunctional system LW
Igema Multifunctional system LW

Application and function

Low water limitation + discontinuous control (with EL913);
only discontinuous control (with EL912)

for processes with limited construction supervision

Water level limiter available for the following conductivity:

0.5-10,000 μS / cm

2-point water level controller DLR1/DHR1

with low alarm (DLR1) or high alarm (DHR1)

2-point water level controller DLR1DHR1
2-point water level controller DLR1DHR1

Application and function

This is, together with IGEMA conductivity probes, a two-point water level controller plus low level alarm (DLR1) or high level alarm (DHR1), to be used in steam boilers or in tanks with conductive liquids.

The product meets EU Directive 2014/658/EU (PED).

Applied rules: corresponding DIN EN standards.

Function DLR1/DHR1

The indicator lamp “UB shows that the power supply is on.

  • Two-point control (pump on-off) by two probes of different length “Pump on” if both probes are out of water, “pump off” if both probes are immersed.
  • Feed control with one probe and one (external) time relay. Only one probe (rod) is needed for pump control. “Pump on” if the probe is out of water and at the same time start of an external time relay. After an adjusted time, the time relay switches “pump off”.
  • Outlet control (flow-off) by two probes of different length “Valve open” when both probes are immersed, “valve closed” when both probes are out of water.

Outlet control: special version as DLR1-A/DHR1-A

Level alarms:

Low level alarm (DLR1)

When the probe is immersed, the relay is energised and the alarm contacts are closed. No alarm (LED “NW”) should be indicated. If the low level probe is out of water, the relay is de-energised and the low level alarm contact opens. The red indicator lamp “NW” lights.

High level alarm (DHR1)

When the probe is out of water, the relay is energised and the alarm contacts are closed. No alarm (LED “HW”) should be indicated. If the low level probe is immersed, the relay is de-energised and the low level alarm contact opens. The red indicator lamp “HW” lights.

Technical basic equipment

  • DLR1/DHR1 is delivered in a plastic plug-in housing for installation in control panels
  • Fixation on standard rail 35 mm according to DIN EN 50022 or directly screwed to chassis plate

Dowload Datasheet: 2-point water level controller DLR1&DHR1

Multiple level probe type EL913

Read more:https://inaparts.com/level-measurement/igema-multifunctional-system-lw/

Tinggalkan Balasan

Please log in using one of these methods to post your comment:

Logo WordPress.com

You are commenting using your WordPress.com account. Logout /  Ubah )

Foto Google

You are commenting using your Google account. Logout /  Ubah )

Gambar Twitter

You are commenting using your Twitter account. Logout /  Ubah )

Foto Facebook

You are commenting using your Facebook account. Logout /  Ubah )

Connecting to %s